Control
Most Outlets and Pumps in the regional models are controlled by a DiscreteControl node. Each has one of these functions, which decides when it lets water through, and the code that adds them is in ribasim_nl.control:
drain: outlet draining an areasupply: inlet supplying an areaflow_control: flow through an area in supply (drought) and drain conditionsflushing: an outlet with a specific flow to be maintained at any conditions (supply or drain)
This is what they do in terms of upstream and downstream levels, in the supply (aanvoer) or drain (afvoer) state:
| Function | Dutch | State determined by | Flow in supply state [m³/s] | Flow in drain state [m³/s] | Nodes added |
|---|---|---|---|---|---|
drain |
uitlaat | upstream level | 0 | capacity | DiscreteControl |
supply |
inlaat | downstream level | capacity | 0 | DiscreteControl |
flow_control |
doorlaat | upstream and downstream level | capacity | capacity | DiscreteControl |
flushing |
doorspoeling | upstream level and flow rate | demand | capacity | DiscreteControl and FlowDemand |
Each controlled node gets two rows in its static table, for the control states aanvoer (supply) and afvoer (drain), and one DiscreteControl node with a control link. The capacity in the table is max_flow_rate: a node lets through its flow_rate, limited by max_flow_rate. Flushing nodes also get a FlowDemand node, which sets the flow to maintain, seasonal if it differs between summer and winter; their flow_rate in the supply state is 0.
Levels and thresholds
The target level of a Basin is its meta_streefpeil in Basin / area. From it follow the thresholds of the DiscreteControl nodes and the level limits of the nodes:
- The thresholds have a band of 5 cm in total around the level (
DEFAULT_LEVEL_THRESHOLD_RANGE), so a node does not keep switching. min_upstream_levelis the target level upstream, and in the supply state 4 cm below it, except for drain nodes, which keep the target level in both states.max_downstream_levelin the supply state is the target level downstream.- In the drain state, Pumps stop pumping into a Basin 20 cm above its target level (
MAALSTOP_LEVEL_OFFSET). Outlets are limited by gravity, so they have no such limit.
The summer and winter levels later split each state into a winter and a summer variant, such as afvoer zomer.
How nodes get their function
The two kinds of models get their function differently.
- Gravity controlled:
04_add_full_control.pycallsadd_controllers_to_supply_areafor each supply area,verwerkt/sturing/aanvoergebieden.gpkg. The inlets and outlets of the polygon, and lists by hand, give the function: inlets supply and outlets drain, the reverse of a supply or flow control node drains, downstream of supply nodes it isflow_control, and the rest drains, except the reverse of a drain node, which supplies. Thenadd_controllers_to_uncontrolled_connector_nodeshandles the remaining Outlets and Pumps, without those inexclude_nodes. The priority is flushing, flow control, drain, supply; the rest again drains, except the reverse of a drain node. - Level controlled: the
meta_categorieof a node maps to a function, with exceptions inset_node_functions. This gives no flushing nodes.
Exceptions
Some systems need more than a DiscreteControl node per connector:
- Noorderzijlvest and Wetterskip Fryslân use
set_continuous_level_controlin places. - Rijnland uses
set_discrete_level_control, with control statesstap n. - Aa en Maas, Limburg and Rijnland also add FlowDemand nodes in their own scripts. In Rijnland, Katwijk flushes at least 1.07 m³/s this way.
- The main water system has its own control with DiscreteControl, ContinuousControl and FlowDemand nodes, see Main water system.
Capacities
The capacity of a node is its max_flow_rate. In the gravity controlled models it comes from the reviewed static_data.xlsx, with flow_rate_mm_per_day as the default by node type and function, and flow_rate is often higher, so max_flow_rate decides. The level controlled models set the unknown capacities from the area they drain or supply, and their flow_rate to the same value, see design capacities.